Tyco Fire Protection Products

IMPORTANT ALERT: VIGILANT/TYCO MX4428 3.10 to V3.21 Firmware
VIGILANT MX4428 or F4000 Fire Alarm Panels with firmware V3.10 to V3.21 (except V3.19) have a latent issue that could cause unexpected changes to the site-specific configuration data when deleting an AAR or MPR point with the panel’s inbuilt programming facility. This could result in addressable devices not generating an alarm, or outputs not operating when required. For further information about this issue and advice on how to detect and rectify, please click on your region below


  NEW ZEALAND
INFORMATION
  AUSTRALIA
INFORMATION
 